966   Range Config - AnalogueValue and scale

Created: 02 Jan 2013

Status: Not Applicable

Part: Part 7-3 (2010; Edition 2)

Links: #929 condition AC_SCAV unclear , #926 Presence Conditions within RangeConfig

Page: 18

Clause: 6.5 Range configuration

Paragraph: Table 6 – Range configuration

Category: No impact on this part

Issue

In addition to Tissue #926 there is another issue with the Type of the hhLim, hLim, lLim, llLim, min, and max: Their type is now AnalogueValue, that means, it could be xxx.i or xxx.f

In case of xxx.i it is not possible to describe which scale and offset is used for the ".i".

Proposal

Solution 1:
Apply the same sVC as for the process values instMag and Mag. This should be explicitly defined in 6.5 Range configuration.

Solution 2:
Define the limits and min/max as INT32U, as is defined for limDb and db.

Discussion Created Status
This is already resolved in TISSUE 929 03 Jan 13 Not Applicable
Proposed solution 3:
Clarify that limits xxx.i correstponds to the xxx.i component of the underlying analog value. It is an error if the limits are specified only as integers and the underlying value is specified only as float and vise-versa.
03 Jan 13 Triage

 

Privacy | Contact | Disclaimer