926 Presence Conditions within RangeConfig

Created
26 Sep 2012
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 7-3 (2010; Edition 2)
Links
#966 Range Config - AnalogueValue and scale
Page
Clause
6.5
Paragraph
Category
Issue may impact interoperability of implementations of Edition 2

Issue

Frim UML Modeling Discussion:
Currently, all attributes of the constructed attibute class "RangeConfig" except limDb are mandatory. However, the attributes min and max are required not only for the range confiuguration, but as well for the interpreation of the db configuration parameter. So there may be a usage of RangeConfig, where main and max are present, but where there is no need for hhLim, hLim, lLim and llLim.

Proposal

Make the attributes hhLim, hLim, lLim and llLim optional as a group (either none or all present)

DiscussionCreated
In Force (green) See Tissue #966 for further issue on RangeConfig. 02 Jan 13
In Force (green) 05 Dec 12
Ballot Period 26 Sep 12