1742 ACSI Client Abort and Release requirements in conformance tableCreated: 10 Dec 2020 Status: Editorial Part: Part 7-2 (2020; Edition 2.1) Links: #1719 Service ID in ACSI conformance statement Page: 179 Clause: A.4 Paragraph: A.3 rows S3-2 and S4-1 Issue Table A.3 (ACSI service conformance statement) shows in row S3-2 optional client requirement to process abort from a server and in row S4-1 mandatory client requirement to issue a release request.
Proposal Change Table A.3 cell(S3-2,Client) from "AtLeastOne(1)" to "M"