1946   Addition of DO Op in LN MFLK

Created: 22 Oct 2024

Status: Approval (N/A)

Part: Part 7-4 (2020; Edition 2.1)

Links: #1947 Addition of DOs in LN QFLK

Page: 181

Clause: 6.10.3

Paragraph: LN: Flicker measurement Name: MFLK

Issue

The LN MFLK is used for operative applications as per its definition. However, several DO are missing to indicate that the flicker levels exceed the threshold settings or to send an alarm to the network control center. This is required to be able to trigger the disturbance recordings in order to analyze the supply quality.

Moreover, as per IEC 61000-4-15:2010, Clause 5.7.1, two settings are defined (Tshort and Tlong) to set the observation periods for flicker computation.
Tshort can be selected between 1 min to 15 min.
Tlong is an integer multiple N of the selected Tshort up to at least 1008.

Proposal

Addition of a DOs :
- Op
- Threshold_Flicker_ShortTerm
- Threshold_Flicker_LongTerm
- Time_Window_ShortTerm
- Time_Window_LongTerm

Discussion Created Status
The discussion of this tissue shall be moved to Part IEC 61850-90-17. So in this section it will be "Not accepted". Please continue to participate in d in section 90-17 (https://iec61850.tissue-db.com/tissues/1947) 13 Nov 24 Approval (N/A)
These DOs belong in an Sxxx Logical Node, perhaps SFLK? 22 Oct 24 Triage

 

Privacy | Contact | Disclaimer