1884 Missing column in table C.1
- Created
- 10 Aug 2023
- Status
- In Force (Editorial)Closed: the editorial correction is part of the standard. No further comments are taken. Show the workflow
- Batch
- 57/2673/INFThis tissue went out with this batch, which was closed on 01 Apr 2024.
- Part
- Part 8-1 (2020; Edition 2.1)
- Links
- None
- Page
- 184
- Clause
- Annex C
- Paragraph
- C.2.4
Issue
Think it is missing column named "Default priority" in Table C.1 in comparison with previous version (IEC 61850-8-1 ed.2.0 2011-06 p.149, Annex C, C.2, table C.1).
Proposal
Add missing column named "Default priority" in Table C.1:
GOOSE - 4.
GSE (deprecated) -1.
Sampled Values - 4.
| Discussion | Created |
|---|---|
| In Force (Editorial) Batch '57/2673/INF' (2) closed | 01 Apr 24 |
| Editorial Approved Editorial | 12 Dec 23 |
|
Approval (Editorial)
Table C.1 was not changed and therefore is not in the AMD document.
IEC made an editorial error in the consolidated version by removing the column. Propose the editorial change in the Consolidated Version Ed2.1 version to restore the column Default Priority with the following value: GOOSE - 4. GSE (deprecated) -1. Sampled Values - 4. One file is attached to this tissue. Sign in to open it. |
22 Aug 23 |