Issue
The conceptual specification indicates:
"The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled."
1) SAV CDC does not contain a data attribute smpRate
2) The Txxx.SmpRte data object indicates how often the value has beeen sampled.
3) the MV/CMV.smpRate attribute inidcates how often the sample has been observed for actualizing the inst component.
Proposal
Modify the clause 6.4.3.1 to indicate that:
The Txxx.SmpRte data object indicates how often the value has beeen sampled.
see tissue #1840
| Discussion | Created |
|---|---|
| In Force (Editorial) Batch '57/2673/INF' (2) closed | 01 Apr 24 |
| Editorial Approved Editorial | 12 Dec 23 |
|
Approval (Editorial)
Editorial change:
Modify the clause 6.4.3.1: Replace: The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled. With: The Txxx.SmpRte data object indicates how often the value has been sampled. |
22 Aug 23 |
|
Approval (Editorial)
This is not a change in CDC, many settings are not writable.
This is an editorial change, following the linked tissue. |
22 Aug 23 |
|
Discussion (red)
TPWG:
Is this a FC change? SmpRte is ING - setting. Change to INS? |
25 Jul 23 |
| Conformance Test Preparation NO issues found, move to CTP | 11 Jul 23 |
| Analysis Of Compatibility No objection, proceed to next state. | 09 Jun 23 |
|
Verify Draft Implementation
Modify the clause 6.4.3.1:
Replace: The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled. With: The Txxx.SmpRte data object indicates how often the value has been sampled. |