1844 Implementation of SumSwARs in 3-phase circuit breaker inaccurateCreated: 12 Sep 2022 Status: Future Improvement Part: Part 7-4 (2020; Edition 2.1) Links: Page: 342 Clause: 6.16.2 LN: Circuit breaker Paragraph: Table 184 Issue For a 3-phase circuit breaker, the sum currents of each individual phase are of interest and not the total sum of all phases. To represent this, four logical XCBR nodes are currently required, one for 3-phase control and three to collect the respective sum currents of the phases. This is confusing because in this case a real circuit breaker is represented by four logical nodes. Proposal By changing the PressCond of SumSwARs from O / O to OMulti / O, three summation currents can also be mapped for a three-phase circuit breaker.