1821 PTDV StrVal DO description
- Created
- 31 Mar 2022
- Status
- In Force (Editorial)Closed: the editorial correction is part of the standard. No further comments are taken. Show the workflow
- Batch
- 57/2673/INFThis tissue went out with this batch, which was closed on 01 Apr 2024.
- Part
- Part 7-4 (2020; Edition 2.1)
- Links
- None
- Page
- 248
- Clause
- 6.11.19
- Paragraph
- Table 120
Issue
The description for the DO StrVal in PTDV looks to be a copy-paste from FrequencyProtectionLN and is not applicable in this LN:
"Frequency or frequency rate change setting; if this
level is exceeded, 'Str.general' becomes true."
Proposal
The description could be:
"Voltage difference start value setting; if this
level is exceeded, 'Str.general' becomes true."
| Discussion | Created |
|---|---|
| In Force (Editorial) Batch '57/2673/INF' (2) closed | 01 Apr 24 |
| Editorial Approve | 11 Oct 22 |
| Approval (Editorial) Change to approval (editorial) | 20 May 22 |
| Discussion (red) The correction should be done with the next bundle of tissues. It is an obvious error. | 07 Apr 22 |
|
Accepted
The tissue is right -> copy/paste error.
Change the description to "Voltage difference start value setting; if this level is exceeded, 'Str.general' becomes true." |
01 Apr 22 |