1821 PTDV StrVal DO description

Created
31 Mar 2022
Status
In Force (Editorial)Closed: the editorial correction is part of the standard. No further comments are taken. Show the workflow
Batch
57/2673/INFThis tissue went out with this batch, which was closed on 01 Apr 2024.
Part
Part 7-4 (2020; Edition 2.1)
Links
None
Page
248
Clause
6.11.19
Paragraph
Table 120

Issue

The description for the DO StrVal in PTDV looks to be a copy-paste from FrequencyProtectionLN and is not applicable in this LN:
"Frequency or frequency rate change setting; if this
level is exceeded, 'Str.general' becomes true."

Proposal

The description could be:
"Voltage difference start value setting; if this
level is exceeded, 'Str.general' becomes true."

DiscussionCreated
In Force (Editorial) Batch '57/2673/INF' (2) closed 01 Apr 24
Editorial Approve 11 Oct 22
Approval (Editorial) Change to approval (editorial) 20 May 22
Discussion (red) The correction should be done with the next bundle of tissues. It is an obvious error. 07 Apr 22
Accepted The tissue is right -> copy/paste error.
Change the description to "Voltage difference start value setting; if this
level is exceeded, 'Str.general' becomes true."
01 Apr 22