1802 Equipment Problem with CB Operating mechanismCreated: 06 Dec 2021 Status: Future Improvement Part: Part 7-4 (2020; Edition 2.1) Links: Page: 306 Clause: 6.14.7 Paragraph: Table 157 Issue The LN SOPM provides multiple alarms for various problems of the Operating mechanism but does not have a DO EEHealth. Proposal Add a DO EEHealth to SOPM (and possibly all condition monitoring LNs) to provide the possibility to have a summary alarm of the Equipment part that is supervised by that LN