1330 proposal in tissue 830 seems not consistent with 7-3 Ed2
- Created
- 14 Nov 2014
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 7-4 (2010; Edition 2)
- Links
- #1331 Mod, Beh and Health with q=TEST, client can't receive their states, #830 Mode/Behaviour & Quality
- Page
- 157
- Clause
- Annex A
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
In tissue 830 a proposal has been accepted:
"Incoming data with q=test+operatorBlocked means validity=good AND test=True AND operatorBlocked=True".
But in IEC61850-7-3, page 14 paragraph 6.2.6, if a data is frozen by operator, so identifier "oldData" shall be set. And according detail quality table, if identifier "oldData" is set, quality has to be "questionable".
Proposal
Modify "Incoming data with q=test+operatorBlocked means validity=good AND test=True AND operatorBlocked=True" by "validity=questionable AND test=True AND operatorBlocked=True".
| Discussion | Created |
|---|---|
| In Force (green) Voting finished and went to green | 20 Jan 15 |
| Ballot Period Changed to Final Proposal | 18 Dec 14 |
|
Discussion (red)
Agree. Additionally change line in tissue #830:
"Incoming data with q=operatorBlocked means validity=good AND test=False AND operatorBlocked=True" by "Incoming data with q=operatorBlocked means validity=questionable AND test=False AND operatorBlocked=True" So in draft of amendment v2.1 part 7-4, annex A, table A.2 two lines will be changed. |
14 Nov 14 |