830 Mode/Behaviour & Quality

Created
09 Mar 2012
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 7-4 (2010; Edition 2)
Links
None
Page
158
Clause
Annex A
Paragraph
Table A.2
Category
Issue for edition 2 of this part

Issue

The quality information "q" in the first column is not consistent with IEC 61850-7-3 Edition 2.
The row "Incoming data with q=normal" does not use the definition of 7-3. In 7-3 the q table 2 has: validity, source, test and operator blocked.

We should use the same language in 7-4 and 7-3.

Proposal


I guess "normal" in "Incoming data with q=normal" means validity=good AND test=False AND operatorBlocked=False.

Incoming data with q=operatorBlocked means validity=good AND test=False AND operatorBlocked=True.

Incoming data with q=test means validity=good AND test=True AND operatorBlocked=False.

Incoming data with q=test+operatorBlocked means validity=good AND test=True AND operatorBlocked=True.

Incoming data with q=invalid means validity=invalid AND test=don't care AND operatorBlocked=don't care.

DiscussionCreated
In Force (green) 07 May 12
Ballot Period 23 Mar 12