1181 Conformance requirement for InformationReport Ambiguous

Created
25 Oct 2013
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 8-1 (2011; Edition 2)
Links
#1626 PICs For Information Report is incorrect
Page
124
Clause
24.2.2.2.2
Paragraph
Table 111
Category
Issue for edition 2 of this part

Issue

The 61850-8-1 Server requirement for InformationReport F/S is marked "c7"

"c7 Shall be 'm' if support for ACSI Report or ACSI command termination is declared."

However, this does not mean that the InitiateResponse.ServicesSupportedCalled should be TRUE to indicate support for InformationReport. According to ISO 9506, the TRUE shall indicate:

"Support of unconfirmed services shallbe defined as the ability to accept and indication primitive and to pass the parameters to the service interface." ISO 9506-1:2011 (also 1990). This means that a TRUE indicates the ability to receive an InformationReport not send it.

Proposal

Clarification needs to be made for the Server component F/S component of InformationReport. Suggest a different conditional or that c7 be refined to indicate the "reception of a Terminate".

A note could also be added that if the sending of the Terminate is required, then the sending of an InformationReport is mandatory. However, this has nothing to do with the setting of the bit in the InitiateResponse.

DiscussionCreated
In Force (green) 15 Apr 14
Ballot Period 05 Mar 14
Discussion (red) I agree with the proposal. 05 Mar 14
Discussion (red) accepted.
Proposal:
c7 for server: shall be 'm' if support for ACSI Report or ControlModel direct control with normal security, direct control with enhanced security, SBO control with enhanced security is declared.
c7 for client: shall be 'm' if support for receive Report or ControlModel direct control with normal security, direct control with enhanced security, SBO control with enhanced security is declared.
05 Dec 13