994 Inconsistent DO name of DCIP.BlowFlow

Created
07 Feb 2013
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 7-420 (2008; Edition 1, DER)
Links
None
Page
19 and 57
Clause
3.2 and 7.1.3
Paragraph
Category
Issue for edition 2 of this part

Issue

The name of DCIP.BlowFlow uses two not declared abbreviations 'Blow' and 'Flow'.

Proposal

- Add the missing abbreviation 'Blow' (for 'Blowby') to the IEC 61850-7-420 abbreviations list.
- Use the existing abbreviation 'Flw' from IEC 61850-7-4.
- Change this DO name to DCIP.BlowFlw
[Decided by WG 17 IEC 61850-7-420 UML Task Force]