992 Inconsistent DO names of DCCT.Currency, DCST.Currency and MFUL.CurrencyCreated: 07 Feb 2013 Status: In Force (green) Part: Part 7-420 (2008; DER) Links: Page: 19, 35, 47, 80 Clause: 3.2, 5.2.7, 6.1.5, 8.1.2 Paragraph: Category: Issue for edition 2 of this part Issue The names of DOs DCCT.Currency, DCST.Currency and MFUL.Currency use a not declared abbreviation 'Currency'. Proposal - Add a new abbreviation 'Ccy' (for 'Currency') to the IEC 61850-7-420 abbreviations list.