937 LCCH.FerCh use for PRPCreated: 24 Oct 2012 Status: In Force (green) Part: Part 7-4 (2010; Edition 2) Links: Page: 25 Clause: 5.3.5 Paragraph: Category: No impact on this part Issue In the NOTE it is described the use of "Fer" (future "FerCh") for detecting wrong connection of cables to ports, based on the following statement: in PRP any message received for a wrong channel is also forwarded to the application. That's not true for 62439-3 Edition 2. Frames received in wrong LAN should be treated as normal frames and duplicates should be discarded. Proposal Remove this statement from the NOTE of LCCH node.