Conflict between -7-4 and -7-420 abbreviations:
- In -7-420: 'Acc' means 'Accumulated'
- In -7-4: 'Acc' means 'Accuracy'
Proposal
Use a non-conflicting abbreviation 'Accm' in -7-420 for 'Accumulated', and change all -7-420 DO names using this abbreviation.
This affects the following data object (DO) names:
- DFPM.InAccWh --> Renamed to DFPM.InAccmWh
- DFPM.OutAccWh --> Renamed to DFPM.OutAccmWh
- MFUL.AccOpTms --> Renamed to MFUL.AccmOpTms
- MFUL.AccTotFuel --> Renamed to MFUL.AccmTotFuel
- MFUL.AccFuel --> Renamed to MFUL.AccmFuel
- MFUL.AccFuelRs --> Renamed to MFUL.AccmFuelRs
- MFUL.AccOpTmRs --> Renamed to MFUL.AccmOpTmRs
- MHET.AccHeatOut --> Renamed to MHET.AccmHeatOut
- MHET.AccHeatCtl --> Renamed to MHET.AccmHeatCtl
[Decided by WG 17 IEC 61850-7-420 UML Task Force]