The data object (DO) name of XFUS.TypFus is inconsistent to all other xxxTyp DO names of IEC 61850-7-420. It should rather spell XFUS.FusTyp.
Furthermore the element names of its type enumeration are far too long for values 1 to 4.
Proposal
- Change DO name of XFUS.TypFus to XFUS.FusTyp.
- Change enumeration element name for value 1 from 'Time-delay fuse: slow-blow explosion fuse' to 'Slow time delay'.
- Change enumeration element name for value 2 from 'Time-delay fuse: fast-blow explosion fuse' to 'Fast time delay'.
- Change enumeration element name for value 3 from 'Fast acting (current limiting fuse)' to 'Fast acting'.
- Change enumeration element name for value 4 from 'Very fast acting (high speed fuse), normally for semiconductors protection' to 'Very fast acting'.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]