906   Inappropriate CDC of DREX.ExtForc

Created: 23 Aug 2012

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page: 48

Clause: 6.2.2

Paragraph:

Category: Issue for edition 2 of this part

Issue

The data object (DO) DREX.ExtForc has CDC ING but its description says "Forced excitation: Yes/no".
A CDC of type SPG would be more appropriate.

Proposal

Change CDC of DREX.ExtForc from ING to SPG.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]

Discussion Created Status
30 Jan 14 In Force (green)
Agreed 17 Oct 13 Ballot Period

 

Privacy | Contact | Disclaimer

Tissue DB v. 24.4.30.1