893   Remove ZBAT, MMET and MENV and use the ones of IEC 61850-7-4 Edition 2

Created: 16 Aug 2012

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page:

Clause: 8.2.2, 8.5.7, 8.5.8

Paragraph:

Category: Issue for edition 2 of this part

Issue

Logical nodes ZBAT, MMET and MENV shall be removed from IEC 61850-7-420 Ed. 2 and be replaced by the identically named LNs from IEC 61850-7-4 Ed. 2.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]
For storage batteries (not auxiliary batteries!) some new Dxxx logical nodes are expected to come from the ongoing from IEC 61850-90-9 Technical Report, which will also be eventually integrated into IEC 61850-7-420 Ed. 2

Proposal

Remove logical nodes ZBAT, MMET and MENV

Discussion Created Status
30 Jan 14 In Force (green)
Agreed 17 Oct 13 Ballot Period
Logical node ZBAT of IEC 61850-7-420 (!) will remain in this standard, but will be renamed to DBAT. See decision made in Tissue 945. 15 Nov 12 Triage

 

Privacy | Contact | Disclaimer

Tissue DB v. 24.4.30.1