874 Logical Node Class needs to be updatedCreated: 30 Jul 2012 Status: In Force (green) Part: Part 7-1 (2011; Edition 2) Links: Page: 87 Clause: 12.2.3 Paragraph: Table 13 Category: Issue for edition 2 of this part Issue The table of the GenLogicalNodeClass definition is not consistent with IEC 61850-7-2 Edition 2, e.g., Log and LogControlBlock are inside the condition (grey box).
Proposal Align table 13 with 7-2 Ed 2 Table 17.