857 Function/SubFunction for ConductingEquipmentCreated: 24 Jun 2012 Status: In Force (green) Part: Part 6 (2009-12; Edition 2) Links: Page: 49 Clause: 9.2.4 Paragraph: Category: Issue may impact interoperability of implementations of Edition 2 Issue Functional naming implies that there are no two logical node references (LNode) of the same LN class at any level within the Substation section. This was one of the reasons for introducing the Function/SubFunction elements.
Proposal Add a Function to tConductingEquipment ant tGeneralEquipment similar to Bay, VoltageLevel or Substation. However, the Function of a ConductingEquipment (or GeneralEquipment) shall differ from the Bay/Function in that it shall not allow to include other ConductingEquipments in order to avoid nested ConductingEquipments (or ConductingEquipments in GeneralEquipments).
Privacy | Contact | Disclaimer Tissue DB v. 24.12.6.1 |