828 Data model namespace revisionCreated: 09 Mar 2012 Status: In Force (green) Part: Part 7-1 (2011; Edition 2) Links: Page: 102 Clause: 13.3.2 Paragraph: Category: Issue for edition 2 of this part Issue It is stated that "Revision refers to a revision indicator. This indicator is required to differentiate revisions
Proposal Clarify that revision A is optional in the namespace name. In other words, "IEC 61850-7-4:2007" is valid and the same as "IEC 61850-7-4:2007A".