810 RFLO LN, extension
- Created
- 29 Dec 2011
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 7-4 (2010; Edition 2)
- Links
- None
- Page
- 85
- Clause
- Paragraph
- 5.13.8
- Category
- Issue for edition 3 of this part
Issue
Logical node RFLO:
For a more efficient use of this logical node two additional data objects are needed:
the fault reactance X and the fault resistance R, both in Ohm.
Proposal
Add two data objects to the LN RFLO "Measured and metered values":
FltX, CDC MV, Fault reactance, mandatory
and
FltR, CDC MV, Fault resistance, mandatory
| Discussion | Created |
|---|---|
| In Force (green) | 05 Mar 12 |
| Ballot Period Accepted | 07 Feb 12 |
| Discussion (red) For backwards compatiblity it would be better that these 2 new DOs are optional. | 05 Jan 12 |