788 SICS S56 from optional to mandatory

Created
20 Oct 2011
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 6 (2009-12; Edition 2)
Links
None
Page
Clause
Annex G
Paragraph
Category
Issue may impact interoperability of implementations of Edition 2

Issue

SCl has introduced the service and engineering capability section to allow a system tool to forbid engineering activities which lead to an SCD file not acceptable by the IED tool respective IED. The current SICS defines this system tool checks as S56 to be optional, however a system tool without this feature will lead to a lot of problems.

Proposal

Make SICS S56 mandatory.

DiscussionCreated
In Force (green) Accepted 20 Jan 12