779 object referencesCreated: 30 Sep 2011 Status: In Force (green) Part: Part 6 (2009-12; Edition 2) Links: Page: Clause: 9.5.4.1 Paragraph: Table 45 Category: Issue may impact interoperability of implementations of Edition 2 Issue 7-4 introduces references to other IEC 61850 objects (LD, LN, DO, DA). In table 45 the values are defined to be according to 7-2. 7-2 only defines absolute names and temporary names. However, e.g. for the GrRef of an LD hierarchy, also IED relative references are needed, as the LD hierarchy is defined per IED type, i.e. before the IED name or its LD name is known. Proposal Introduce IED relative object references e.g. as @ldInst/lnName[.doName] with the ldInst value as defined in SCL, for use in references on the same IED as the referenced object.