739   Terminal connection

Created: 13 Jul 2011

Status: Not Applicable

Part: Part 6 (2004)

Links:

Page: 38

Clause: 9.2.3

Paragraph:

Category: No impact on this part

Issue

Why SAR (see table 5, page 38) has just one Terminal element? SAR has to be grounded, therefore be connected on one side to the
connectivity node grounded and has two Terminal elements.

Proposal

SAR has to contain two Terminal elements.

Discussion Created Status
It is assumed that one side of SAR is always grounded, therefore no second terminal is provided. 28 Sep 11 Not Applicable

 