734 LLN0.OpTmh vs. LPHD.OpTmh
- Created
- 26 May 2011
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 7-4 (2010; Edition 2)
- Links
- None
- Page
- Clause
- 5.3.4
- Paragraph
- Category
- Issue may impact interoperability of implementations of Edition 2
Issue
In LN LLN0 there is modelled DO OpTmh. The semantic is not clear. If we want to express the time how long the IED is in operation OpTmh should be moved into LPHD.
Proposal
Move OpTmh from LLN0 to LPHD (optional)(proposal from WG10 meeting in Seoul).
| Discussion | Created |
|---|---|
| In Force (green) | 15 Sep 11 |
| Ballot Period Accepted | 05 Aug 11 |
| Discussion (red) Meant is OpTmh | 20 Jul 11 |
| Discussion (red) Accepted to move OpTmH from LLN0 to LPHD and change the description as follows: Operation time since last power up. | 20 Jul 11 |
| Discussion (red) | 26 May 11 |