704 MFUL AccOpTmRs CDC
- Created
- 03 Jan 2011
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 7-420 (2008; Edition 1, DER)
- Links
- None
- Page
- 80
- Clause
- 8.1.2
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
But why is a DPC needed? This is a simple reset.
Proposal
Change to SPC
| Discussion | Created |
|---|---|
|
In Force (green)
- Duplicate of Tissues 646 and 651
- The name of data objects AccFuelRs and AccOpTmRs have been changed to AccmFuelRs and AccmOpTmRs, resp - see Tissue 922 - The common data class (CDC) for these data objects have been changed to SPC - see Tissue 894 - The logical node MFUL has been renamed to SFUL and moved to IEC 61850-7-4 Ed. 2.1 - see Tissue 1218 |
03 Mar 14 |
| In Force (green) | 30 Jan 14 |
| Ballot Period Agreed | 20 Oct 13 |
| Triage The CDC of this DO will be changed to SPC in edition 2 - see tissue 894. | 16 Aug 12 |