702 MFUL AccFuelRs M/O
- Created
- 03 Jan 2011
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 7-420 (2008; Edition 1, DER)
- Links
- None
- Page
- 80
- Clause
- 8.1.2
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
Why is MFUL.AccFuelRs mandatory?
Proposal
Change to optional
| Discussion | Created |
|---|---|
|
In Force (green)
- Duplicate to Tissue 650
- The name of data objects AccFuel and AccFuelRs have been changed to AccmFuel and AccmFuelRs, resp - see Tissue 922 - The logical node MFUL has been renamed to SFUL and moved to IEC 61850-7-4 Ed. 2.1 - see Tissue 1218 - The presence condition of data object AccmFuelRs has been changed to O (optional) in logical node SFUL of IEC 61850-7-4 Ed. 2.1 |
03 Mar 14 |
| In Force (green) | 30 Jan 14 |
| Ballot Period Agreed | 20 Oct 13 |