656   Mapping of negative ENUMERATED as private is in contradiction with IEC61850-7-3 Table A.5 (Unit mult

Created: 30 Dec 2009

Status: Not Applicable

Part: Part 8-1 (2004)

Links:

Page: 34

Clause: 8.1.2.2

Paragraph:

Category: Issue for edition 2 of this part

Issue

8.1.2.2 states "Values that are less than 0 shall be considered private values. The range of allowed values
are specified in IEC 61850-7-2 and IEC 61850-7-3" while IEC61850-7-3 Table A.5 states negative values for (some) unit multipliers.

Proposal

Remove statement "Values that are less than 0 shall be considered private values.".

Discussion Created Status
A note has been added about the unit multiplier exception.
8-1 can not remap the value of 7-3. However the statement is still correct for other enumerations
16 Jun 10 Not Applicable

 