655   EntryID

Created: 19 Nov 2009

Status: Not Applicable

Part: Part 8-1 (2004)

Links:

Page: 35

Clause: 8.1.3.4

Paragraph:

Category: Issue for edition 2 of this part

Issue

Part 8-1 clause 8.1.3.4 states that EntryID should be mapped to an 8 OCTET FIXED LENGTH string, while Part 7-2 clause 14.2.2.15 states ARBITRARY octet string that does not imply length.

Proposal

Change either part 8-1 or part 7-2 in order to be consistent with each other.

Discussion Created Status
Part 7-2 leaves to the SCSM the format of the ENTRY ID. The documents are consistent. 8-1 maps the EntryID type to an 8 octet fixed length string 16 Jun 10 Not Applicable

 