648   Battery charger ZBTC Common Data Class SCH undefined

Created: 01 Sep 2009

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page:

Clause: 8.2.3

Paragraph:

Category: Issue for edition 2 of this part

Issue

For the Data Object ChaCrvTim the Common Data Class SCH is defined. This Data Class however doesn't exist.
This shouldn't work successful.

Proposal

Should this be something like a time schedule?

Discussion Created Status
- The data object ChaCrvTim has been renamed to ChaCrvTm (see Tissue 1009), has now a common data class SCR (see Tissue 896) and is now in logical node DBTC (see Tissue 945).
- Decided in the Fredericia meeting of Feb. 2014 that this Tissue should go to green state now.
28 Feb 14 In Force (green)
This CDC will be changed to SCR - see tissue 896.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]