647   Battery Systems ZBAT Common Data Class SCH undefined

Created: 01 Sep 2009

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page:

Clause: 8.2.2

Paragraph:

Category: Issue for edition 2 of this part

Issue

For the Data Object DisChaTim the Common Data Class SCH is defined. This Data Class however doesn't exist.
This shouldn't work successful.

Proposal

Should this be something like a time schedule?

Discussion Created Status
- The data object DisChaTim has been renamed to DschTm (see Tissue 1019), has now a common data class SCR (see Tissue 896) and is now in logical node DBAT (see Tissue 945).
- Decided in the Fredericia meeting of Feb. 2014 that this Tissue should go to green state now.
28 Feb 14 In Force (green)
Analoguous to Tissues 896 and 648 the CDC of DO DisChaTim shall be changed to SCR.
[Decided by WG 17 IEC 61850-7-420 UML Task Force]
Please note the LN ZBAT has been renamed to DBAT, see Tissue 945.
The prior decision in Tissue 893 has been reverted and is no more relevant.
15 Nov 12 Triage
No more relevant as it was decided by the WG 17 IEC 61850-7-420 UML Task Force to remove LN ZBAT from 61850-7-420 Ed. 2 and to replace it by the identically named LN from 61850-7-4 Ed. 2 - see tissue 893. 16 Aug 12 Triage

 