646   Fuel characteristics MFUL Data Objects Common Data Class DCP undefined

Created: 01 Sep 2009

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page:

Clause: 8.1.2

Paragraph:

Category: Issue for edition 2 of this part

Issue

For the Data Objects AccFuelRs and AccOpTmRs the Common Data Class DCP is defined. This Data Class however doesn't exist.
This shouldn't work successful.

Proposal

Should this be the Data Class DPC instead of DCP?

Discussion Created Status
Some more comments:
- The name of data objects AccFuelRs and AccOpTmRs have been changed to AccmFuelRs and AccmOpTmRs, resp - see Tissue 922
- The logical node MFUL has been renamed to SFUL and moved to IEC 61850-7-4 Ed. 2.1 - see Tissue 1218
27 Feb 14 In Force (green)
30 Jan 14 In Force (green)
Accept proposal from UML TF 08 Oct 13 Ballot Period
The CDC of this DO will be changed to SPC in edition 2 - see tissue 894. 16 Aug 12 Triage

 

Privacy | Contact | Disclaimer