590 Data object ErrTerm
- Created
- 08 Jan 2008
- Status
- Discussion (red)Open for discussion while the solution is worked out. Any signed-in reader may comment. Show the workflow
- Part
- Part 7-410 (2007; Hydro Power)
- Links
- None
- Page
- 7.2
- Clause
- LNs FFIL, FPID, FRMP, FSPT
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
The ErrTerm data object is used to indicate that the output of a control function has been limited due to some internal restriction. ErrTerm is stated to be of CDC MV. It is actually a status indication and should be of CDC SPS.
Proposal
In Logical Nodes FFIL, FPID, FRMP and FSPT, change Common Data Class for ErrTerm to be SPS instead of MV.
| Discussion | Created |
|---|---|
| Discussion (red) refused, ErrTerm rmains MV, included better desription in semantic table | 13 Mar 08 |
| Triage Should remain MV. ErrTerm is a mathematical result of a Error term calculation. See figure A3. | 28 Jan 08 |