563 RSYN

Created
15 Oct 2007
Status
Discussion (red)Open for discussion while the solution is worked out. Any signed-in reader may comment. Show the workflow
Part
Part 7-410 (2007; Hydro Power)
Links
None
Page
Clause
7.8.2
Paragraph
Category
Issue for edition 2 of this part

Issue

Conditional inclusions are not described. For example, when is RV required?

Proposal

Specify conditional inclusions throughout document. EVERY ā€œCā€œ in the M/O/C column needs an explanation

DiscussionCreated
Triage The Conditionsals should be called C1 and C2. C1 is applicable for the first conditional (Rel), with the text that is written in parantesis in the explanation.

C2 is applicable for the others (Cmd, RV, LV, RHz and LHz) with the text that is written in parantesis in the explanation of Cmd.
22 Oct 07