561 LN KVLV.Cls
- Created
- 15 Oct 2007
- Status
- TriageNew, and not yet classified. The working group decides whether to take it forward as a technical issue or to close it. Show the workflow
- Part
- Part 7-410 (2007; Hydro Power)
- Links
- None
- Page
- Clause
- 7.5.6
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
Cls as CDC DPC makes no sense. Feedback value can never be “intermediate“
Proposal
Change to CDC SPC. Feedback TRUE=fully closed, FALSE=otherwise