561 LN KVLV.Cls

Created
15 Oct 2007
Status
TriageNew, and not yet classified. The working group decides whether to take it forward as a technical issue or to close it. Show the workflow
Part
Part 7-410 (2007; Hydro Power)
Links
None
Page
Clause
7.5.6
Paragraph
Category
Issue for edition 2 of this part

Issue

Cls as CDC DPC makes no sense. Feedback value can never be “intermediate“

Proposal

Change to CDC SPC. Feedback TRUE=fully closed, FALSE=otherwise