558   LN KPMP.Operate

Created: 15 Oct 2007

Status: Discussion (red)

Part: Part 7-410 (2007; Hydro Power)

Links:

Page:

Clause: 7.5.4

Paragraph:

Category: Issue for edition 2 of this part

Issue

Operate as CDC DPC makes no sense. Feedback value can never be “intermediate“

Proposal

Change to CDC SPC

Discussion Created Status
Operating SPC is like DPC: Writing Oper.ctlVal=TRUE sets TRUE/ON, writing FALSE sets FALSE/OFF. No reason for two controls... 19 Oct 07 Discussion (red)
By changing to SPC, we need two controls, one for on and one for off. 19 Oct 07 Triage

 

Privacy | Contact | Disclaimer

Tissue DB v. 24.12.4.1