558 LN KPMP.Operate

Created
15 Oct 2007
Status
Discussion (red)Open for discussion while the solution is worked out. Any signed-in reader may comment. Show the workflow
Part
Part 7-410 (2007; Hydro Power)
Links
None
Page
Clause
7.5.4
Paragraph
Category
Issue for edition 2 of this part

Issue

Operate as CDC DPC makes no sense. Feedback value can never be “intermediate“

Proposal

Change to CDC SPC

DiscussionCreated
Discussion (red) Operating SPC is like DPC: Writing Oper.ctlVal=TRUE sets TRUE/ON, writing FALSE sets FALSE/OFF. No reason for two controls... 19 Oct 07
Triage By changing to SPC, we need two controls, one for on and one for off. 19 Oct 07