552 HMBR-Controls

Created
15 Oct 2007
Status
Discussion (red)Open for discussion while the solution is worked out. Any signed-in reader may comment. Show the workflow
Part
Part 7-410 (2007; Hydro Power)
Links
None
Page
Clause
Paragraph
Category
Issue for edition 2 of this part

Issue

HMBR.Pos is indicated as DPC

Proposal

Should be SPC

DiscussionCreated
Discussion (red) Operating SPC is like DPC: Writing Oper.ctlVal=TRUE sets TRUE/ON, writing FALSE sets FALSE/OFF. No reason for two controls... 19 Oct 07
Triage If we change to SPC, we need two controls, one to engage the brake and a second to disengage the brake. It seems simpler to keep the function as DPC. 19 Oct 07