436 Overturn Tissue 173Created: 26 Oct 2006 Status: Not Applicable Part: Part 6 (2004) Links: Page: Clause: Paragraph: Category: Issue for edition 2 of this part Issue Tissue 173 should not have been entered as a General tissue. It reverses previous decisions made on 8-1 and does not allow control structures to be specified in SCL.
Proposal Overturn the resolution of 173, put the CO structures back into 7-3 so that they can be properly specified in SCL. The SCL specification of the attributes must be backward compatible with the old SCL and structures of 7-3 prior to tissue 173 resolution