313   number of terminals for the type code PTW

Created: 13 Apr 2006

Status: In Force (green)

Part: Part 6 (2004)

Links:

Page: 38

Clause: 9.2.3

Paragraph: Table 5

Category: Issue for edition 2 of this part

Issue

In table 5 the number of terminals (connections to different connectivity nodes) for the type code PTW (Power Transformer Winding) is limited to only one terminal.
In case of a grounded starpoint, for example with an additional CTR, the starpoint of a winding represents a second terminal.

Proposal

The number of terminals for the type code PTW should be two.

Discussion Created Status
08 Aug 06 In Force (green)
The number of allowed terminals for PTW will be increased to two. The Terminal element gets an attribute 'neutralpoint' with default value 'false', which must be set to 'true' on one of the two PTW Terminals. 16 Jun 06 Ballot Period

 

Privacy | Contact | Disclaimer