262 LastApplError Error codes
- Created
- 18 Nov 2005
- Status
- In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
- Part
- Part 8-1 (2004)
- Links
- None
- Page
- 88
- Clause
- 20.8
- Paragraph
- Category
- Issue for edition 2 of this part
Issue
Part 8-1 defines LastApplError to have component named Error and its ENUM values. It is however not defined how these values should be used.
Proposal
| Discussion | Created |
|---|---|
| In Force (green) changed to green | 13 Jan 06 |
|
Ballot Period
The text should be modified to indicate:
TimeOut Test Not OK shall be returned if a TimeActivated Control CMD is issued, with TEST=TRUE, and the operation fails. Operator Test Not OK shall be retunred if an OPER control CMD is issued, with TEST=TRUE, and the operation fails. |
02 Dec 05 |
|
Not Applicable
When to use LastApplError is defined in IEC 61850-7-2. In 61850-7-2, this is detailed as AddCause.
Therefore, to find out when to send 8-1's LAstApplError, 7-2 is the specification. |
18 Nov 05 |