20 Store settings valuesCreated: 30 Jan 2005 Status: Not Applicable Part: Part 6 (2004) Links: Page: Clause: 9.3.12 Paragraph: Category: No impact on this part Issue We have not found by any way how to store via the .SCD file the values of parameters for each setting group block. We do not know if it is a misunderstanding. If not, it will not be possible to have as standardized way the values for the different setting groups in order to automate the download for both configuration and parametrization. It it is done manually on-line, and then, the stored information need to be kept in a private extension of the .CID file Proposal To extend the possibilities for defining each value for each parameter within each setting group.
Privacy | Contact | Disclaimer Tissue DB v. 24.12.6.1 |