1887 VSpt in DEXC
- Created
- 05 Sep 2023
- Status
- Drafting ImplementationThe agreed solution is being written up as text for the standard. Any signed-in reader may comment. Show the workflow
- Part
- Part 7-420 (2021; Edition 2, DER)
- Links
- None
- Page
- 312
- Clause
- A.3.1.15.3
- Paragraph
- Table A.61
Issue
VSpt is defined as ASG in DEXC but I think it should be APC because the DO represents a (control) setpoint.
Proposal
VSpt should be defined for controls and typed with APC.
| Discussion | Created |
|---|---|
| Drafting Implementation 14-November-2025 Agree to change to APC | 14 Nov 25 |
| Discussion (red) Accepted for discussion | 04 Nov 25 |
| Accepted Accepted | 04 Nov 25 |
|
Triage
Agree - change to APC
This is also consistent with IEC 61400-25-2 Issue also detected by j61850DocBuilder v2.04 [main] INFO Found issues - by validating: IEC 61850 LN attributes (DO) with same names but different type (CDC) - Fix: rename (DO) attribute OR change its type (CDC): [main] ERROR IEC61850_7_420 DERExcitationLNs::DEXC.VSpt : [[ IEC61850_7_420 DERExcitationLNs::DEXC.VSpt] is ASG, [IEC61400_25_2 WindPowerPlant::WRPC.VSpt] is APC] |
13 Feb 25 |