179 IED parameters not exposed in object modelsCreated: 04 Aug 2005 Status: Discussion (red) Part: General Links: Page: Clause: Paragraph: Category: Issue for edition 2 of this part Issue This expands the issue raised in Tissue 139. There are several parameters resident in the IEDs that are not exposed via the object models in Parts 7, 8, and 9, although they are managed by SCL in Part 6. These include the clients to which reports are to be addressed, the maxima of allowable data sets and reports, and identification of whether certain data values are settable by the client.
Proposal Include the relevant parameters in the object models of Parts 7, 8, and 9.