[1] and [APPLICATION 0] will not result in the same binary BER
representation.
Proposal
Harmonize 9-1 and 9-2.
Based on 9-1 comments in Clause 7.3.1 (value of the tag equal to 0x80
for 9-1) and examples in 9-2, Annex A.3 (value of the tag equal to
0x60 for 9-2), it seems that the definition given in 9-2 satisfies
both.
Discussion
Created
Status
IEC 61850-9-1 shall be changed as follows:
IecSavPdu ::= CHOICE { 9-1-Pdu [0] IMPLICIT OCTET STRING,
-- Used for 9-1 APDU
savPdu [APPLICATION 0] IMPLICIT SavPdu,