1740 Exceptions of enumeration types for IEC 61850-7-4
- Created
- 24 Nov 2020
- Status
- In Force (Editorial)Closed: the editorial correction is part of the standard. No further comments are taken. Show the workflow
- Batch
- 57/2673/INFThis tissue went out with this batch, which was closed on 01 Apr 2024.
- Part
- Part 6 (2019; Edition 2.1)
- Links
- #1726 Enumeration ClockSyncKind of LTMS.TmSyn is not correct
- Page
- 128
- Clause
- 9.5.6
- Paragraph
- last in 9.5.6
Issue
In section 9.5.6 is defined:
"The ord attribute contains the order of the values, with some exceptions explicitly defined in IEC 61850-7-3 starting from 0 for enumerations from IEC 61850-7-3, and from 1 for enumerations from IEC 61850-7-4."
Some exception shall also be allowed for part 7-4 (e.g. ClockSyncKind).
Proposal
Change the statement to:
"... with some exceptions explicitly defined in IEC 61850-7-3 or in IEC 61850-7-4..."
| Discussion | Created |
|---|---|
| In Force (Editorial) Batch '57/2673/INF' (2) closed | 01 Apr 24 |
| Editorial Approved Editorial | 03 Jun 21 |
| Approval (Editorial) editorial change to be done in AMD 2.2 | 22 Feb 21 |
|
Triage
I agree and I think the tissue can be seen as editorial one.
The statement in part 6 is informative and has no impact on implementations. |
11 Feb 21 |