1593 QMSV missing in Figure 22Created: 14 Jul 2017 Status: In Force (green) Part: Part 90-17 (2017; Ed1, Power Quality Data) Links: Page: 45 Clause: 6.2.2 Paragraph: Category: Issue for edition 2 of this part Issue In "Figure 22 – State of the art data modeling for use case "Sending of power quality events/limit violations"" the QMSV block is not shown. According to "Table 27 - PQ mapping" it should be present. Proposal Add the QMSV block to Figure 22.