156 GOOSE / GSSE sqNum
- Created
- 11 Apr 2005
- Status
- Ballot PeriodIn the formal ballot, gathering the final votes and comments. Any signed-in reader may comment. Show the workflow
- Part
- Part 10 (2005)
- Links
- None
- Page
- 29
- Clause
- 6.2.4.13.1 Table 29
- Paragraph
- Goo4
- Category
- Issue for edition 2 of this part
Issue
Upon resolution of TISSUE 52 (in part 7-2), the positive test case for the GOOSE/GSSE sqNum value upon stNum change will need revision.
Proposal
Change "Verify for GOOSE and GSSE that sqNum and stNum have the initial value one (1)..." to "Verify for GOOSE and GSSE that sqNum and stNum have the initial value zero (0)..."
| Discussion | Created |
|---|---|
|
Ballot Period
Part 7-2 Ed2 CDV states that the initial stNum = 1 and initial sqNum is "recommended" = 0. This overrules tissue 52. The test procedure for edition 1 (Gop3) will be changed accordingly.
Note: at boottime of an IED a managed Ethernet switch needs some time to initialize the connection and will drop several initial messages from the IED |
29 Sep 08 |