143 Time activated responses

Created
01 Apr 2005
Status
In Force (green)Closed: the solution is part of the standard. No further comments are taken. Show the workflow
Part
Part 8-1 (2004)
Links
None
Page
83
Clause
Paragraph
Table 69
Category
Issue for edition 2 of this part

Issue

The mapping of the time activated operated include 2 identical information reports:
2nd response,
command termination.
Both are carrying the same ListOfVariable: "Oper".
There is no chance to distinguish them.

Proposal

Please make them different.

DiscussionCreated
In Force (green) Actual changes need to be made in clause 20.7.2 and 20.9 16 Feb 06
In Force (green) changed to green 13 Jan 06
Ballot Period Change clause 20.9 to mandate that the CMDTerm_req+ shall have the value of OperTm=0. This value shall be used to indicate CMDTermination. 02 Dec 05
Discussion (red) The issue needs to be considered together with Fig 37 of 7-2.

When using Time activated control, the sequence of responses is as follows:

7-2 8-1
TimOper_rsp+ Write response (Success)
TimOper_rsp+ InformationReport(Oper)
CmdTerm_req+ InformationReport(Oper)

It is the last two 8-1 messages that can not be distinguished.
20 Sep 05